Chapter 6 CP 240 - M-Bus
Manual VIPA System 200V
6-14
HB97E - CP - Rev. 11/30
The example uses the following data blocks:
Addr. Name
Type
Comment
0.0
STRUCT
+0.0
Sendefach
STRUCT
Send data block
+0.0
Baudrate
BYTE
B8h=300, BBh=2400, BDh=9600
+1.0
OK / C-Feld
BYTE
E5h=OK / C field
+2.0 A-Feld
BYTE
A
field
+3.0 CI-Feld
BYTE
CI
field
+4.0
User-Data Byte 0
BYTE
...
+252.0 User-Data Byte 247
BYTE
Transfer complete
+253.0 Reserve
BYTE
+254.0 Anzahl
WORD
Transmitting
length
+256.0 gesendet
WORD
Already sent data
+258.0 Byte_Zaehler
WORD
Transmitting length (internal)
+260.0 Kom_Ende
BOOL
Telegram transmitted completely
+260.1 LB
BOOL
Last block has been sent
+260.2 SL
BOOL
Still
transmitting
+260.3 Fehl
BOOL
Error during transmission
+260.4 Senden_Start
BOOL
Start
bit
+261.0 PAFE
BYTE
Parameterization
error
=262.0
END_STRUCT
Addr. Name
Type
Comment
0.0
STRUCT
+0.0
Data
ARRAY [0..100]
*1.0
Byte
+102.0 Anzahl
WORD
Amount of received data
+104.0 empfangen
WORD
Already received data
+106.0 Byte_Zaehler
WORD
Amount of received bytes (internal)
+108.0 Empf_laeuft
BOOL
Still
receiving
+108.1 LB
BOOL
Last block has been received
+108.2 Fehl
BOOL
Error during reception
+108.3 Reserve
BOOL
+108.4 Empfang fertig
BOOL
Reception ready
+109.0 PAFE
BYTE
Parameterization error
=110.0
END_STRUCT
Data blocks
DB10
SEND data block
DB11
RECEIVE data block
Summary of Contents for CP 240 RS232
Page 1: ...Manual VIPA System 200V CP Order No VIPA HB97E_CP Rev 11 30...
Page 2: ...L...
Page 14: ...Chapter 1 Basics Manual VIPA System 200V 1 6 HB97E CP Rev 11 30...
Page 126: ...Chapter 5 CP 240 EnOcean Manual VIPA System 200V 5 32 HB97E CP Rev 11 30...
Page 144: ...Chapter 6 CP 240 M Bus Manual VIPA System 200V 6 18 HB97E CP Rev 11 30...
Page 148: ...Index Manual VIPA System 200V A 4 HB97E CP Rev 11 30 M Stich...