Manual VIPA System 200V
Chapter 4 CP 240 - serial
HB97E - CP - Rev. 11/30
4-21
Byte Function
Range of values
Default
parameters
0
Baud rate
00h: Default (9600Baud)
01h: 150Baud
02h: 300Baud
03h: 600Baud
04h: 1200Baud
05h: 1800Baud
06h: 2400Baud
07h: 4800Baud
08h: 7200Baud
09h: 9600Baud
0Ah: 14400Baud
0Bh: 19200Baud
0Ch: 38400Baud
0Dh: 57600Baud
0Fh: 76800Baud
0Eh: 115200Baud
00h: 9600Baud
1 Protocol
03h:
3964
04h: 3964R
05h: 3964 + RK512
06h: 3964R + RK512
03h: 3964
2 Bit
1/0
Data bits
00b: 5 Data bits
01b: 6 Data bits
10b: 7 Data bits
11b: 8 Data bits
11b: 8 Data bits
Bit
3/2
Parity
00b: none
01b: odd
10b . even
11b: even
00b: none
Bit
5/4
Stop bits
01b: 1
10b: 1.5
11b: 2
01b: 1 Stop bit
Bit
7/6
Flow control
reserved -
3 reserved
0
0
4 ZNA
(*20ms)
0..255
0
5 ZVZ
(*20ms)
0..255
10
6 QVZ
(*20ms)
0..255
25
7 BWZ
(*20ms)
0..255
100
8 STX
repetitions
0..255
5
9 DBL
0..255
6
10 Priority
0:
low
1: high
0: low
11 reserved
12 reserved
13 reserved
14 reserved
15 reserved
Structure of
parameter bytes for
3964(R) / 3964(R)
with RK512
Summary of Contents for CP 240 RS232
Page 1: ...Manual VIPA System 200V CP Order No VIPA HB97E_CP Rev 11 30...
Page 2: ...L...
Page 14: ...Chapter 1 Basics Manual VIPA System 200V 1 6 HB97E CP Rev 11 30...
Page 126: ...Chapter 5 CP 240 EnOcean Manual VIPA System 200V 5 32 HB97E CP Rev 11 30...
Page 144: ...Chapter 6 CP 240 M Bus Manual VIPA System 200V 6 18 HB97E CP Rev 11 30...
Page 148: ...Index Manual VIPA System 200V A 4 HB97E CP Rev 11 30 M Stich...