Additional information
124
Coding 2
(continued)
Overview of all codings
(continued)
Coding as per
factory
setting
Address: Value
Function
New coding
Address:
Value
Possible change
78: 1
General
LON communication
released
78: 0
LON communication blocked
79: 1
General
Control unit is fault manager 79: 0
Control unit is not fault manager
7A: 0
General
Without centralized
7A: 1
With centralized operation of system circuit A1
operation of the heating
circuits
7A: 2
With centralized operation of mixing valve
circuit M2
7A: 3
With centralized operation of mixing valve
circuit M3
7b: 0
General
Do not transmit time via
LON BUS
7b: 1
Transmit time via LON BUS
7F: 1
General
Single occupancy house
7F: 0
Multi-occupancy house
80: 6
General
With 5 seconds time delay
80: 0
Without time delay
y
for fault message
80: 2
to
80: 199
Time delay adjustable between
10 and 995 seconds;
1 increment = 5 seconds
81: 1
General
Automatic resetting to
summer/winter time
81: 0
Manual resetting to summer/winter time
summer/winter time
Please note:
Codings ”82” to ”87” are
l
ibl if
di
”81
81: 2
Use of radio clock module automatically
recognized
only possible if coding ”81 :
1” is set.
81: 3
Receive time from LON
82: 3
General
Start of summer time:
March
82: 1
to
82: 12
January
to
December
83: 5
General
Start of summer time:
last week of month
83: 1
to
83: 4
Week 1
to
Week 4 of the selected month
84: 7
General
Start of summer time:
last day of week
(Sunday)
84: 1
to
84: 7
Monday
to
Sunday
85: 10
General
Start of winter time:
October
85: 1
to
85: 12
January
to
December
86: 5
General
Start of winter time:
last week of month
86: 1
to
86: 4
Week 1
to
Week 4 of the selected month
87: 7
General
Start of winter time:
last day of week
(Sunday)
87: 1
to
87: 7
Monday
to
Sunday