Additional information
131
Coding 2
(continued)
Overview of all codings
(continued)
Coding as per
factory setting
Address:
Value
Function
New coding
Address:
Value
Possible change
C0: 0
*1
Boiler
circuit/
mixing
In conjunction with remote
control:
Without optimized switch-off
C0: 1
With optimized switch-off time (max. time
shift 1 hour)
mixing
valve
circuit
Without optimized switch-off
time
C0: 2
With optimized switch-off time (max. time
shift 2 hours)
C1: 0
*1
Boiler
circuit/
mixing
valve
circuit
In conjunction with remote
control:
Without optimized switch-off
time
C1: 1
to
C1: 12
With optimized switch-off time (max. time
shift from 10 to 120 minutes)
1 increment = 10 minutes
C2: 0
*1
Boiler
circuit/
mixing
valve
circuit
Without learning optimized
switch-off time
C2: 1
With learning optimized switch-off time
C3: 125
Mixing
valve
circuit
Operating time of mixing
valve 125 seconds
C3: 10
to
C3: 255
Operating time adjustable from
10 to 255 seconds
C4: 1
Mixing
valve
Mixing valve circuit with
4-way mixing valve
C4: 0
Mixing valve circuit with 3-way
mixing valve
circuit
y
g
C4: 2
Special case 1
C4: 3
Special case 2
C5: 20
Boiler
circuit/
mixing
valve
circuit
Electronic minimum supply
temperature limit 20°C /
68°F
C5: 1
to
C5: 127
Electronic minimum limit variable between
1 and 127°C / 34 and 261°F
C6: 75
Mixing
valve
circuit
Electronic maximum supply
temperature limit set to
75°C
C6: 10
to
C6: 127
Electronic maximum limit variable between
1 and 127°C / 34 and 261°F
C8: 31
Boiler
circuit/
mixing
valve
circuit
In conjunction with remote
control:
Without limit on room
influence
C8: 1
to
C8: 30
Limit on room influence variable from 1 to
30 K
d5: 0
Boiler
circuit/
mixing
valve
circuit
Heating program switches
over to ”Continuous
operation” with reduced
room temperature
d5: 1
Heating program switches over to
”Continuous space heating” with normal
room temperature
E1: 1
Boiler
circuit/
mixing
In conjunction with remote
control:
Day setpoint value variable
E1: 0
Day setpoint value variable from
3 to 23°C
mixing
valve
circuit
Day setpoint value variable
from 10 to 30°C
E1: 2
Day setpoint value variable from
17 to 37°C
5285
941
-
0