Installation
28
Connection of the return temperature sensor
Strap-on temperature sensor and immersion temperature sensor
For measuring the boiler return
temperature.
Electrical connection
The sensor is inserted in socket
”17A” or ”17B” on the boiler
control.
Check the sensor
1.
Disconnect plug
aJ
A
or
aJ
B
in the terminal compartment of
the boiler control.
2.
Measure resistance of sensor
at terminals ”1” and ”2” of the
plug.
Return
temperature
in °C / °F
Resistance
in
30 / 86
40 / 104
60 / 140
569
592
643
3.
Compare the value measured
with the current temperature. If
the value differs significantly,
check installation and, if
necessary, replace sensor.
Technical data
Degree of protection: IP 32
Ambient temperature
During operation:
0 to + 100°C
32 to + 212°F
During storage and transport:
-20 to + 70°C
-4 to + 158°F