Additional information
114
Coding 1
Call up coding level 1
Only those coding addresses are displayed which correspond to the system type
and equipment concerned and can be changed accordingly.
1.
Press
9
and
w
simultaneously for
approx. 2 seconds.
Access coding level 1.
2.
Call up the required coding address
with the
or
button;
press
to confirm.
3.
Change the value with the
or
button;
press
to confirm.
4.
Press
9
and
w
simultaneously for
approx. 1 second.
Address flashes.
Value flashes.
”Accepted” appears briefly in the
display, then the address flashes
again. Further addresses can now be
selected with the
or
button.
Exit coding level 1.
Codings
Function
Coding as per factory setting
Address: Value
Possible change
System type
00: 1
System circuit A1,
without domestic hot water heating
00:
1
2
System circuit A1,
with domestic hot water heating
without domestic hot water heating
00:
1
3
Mixing valve circuit M2,
without domestic hot water heating
00:
1
4
Mixing valve circuit M2,
with domestic hot water heating
00:
1
5
System circuit A1 and mixing valve circuit
M2,
without domestic hot water heating
00:
1
6
System circuit A1 and mixing valve circuit
M2,
with domestic hot water heating
00:
1
7
Mixing valve circuits M2 and M3,
without domestic hot water heating
00:
1
8
Mixing valve circuits M2 and M3,
with domestic hot water heating
00:
1
9
System circuit A1 and mixing valve circuits
M2 and M3, without domestic hot water
heating
00: 10
System circuit A1 and mixing valve circuits
M2 and M3, with domestic hot water
heating
5285
941
-
0
1
Coding 1
Cod. 1
System type
Cod. 1