Additional information
93
Technical data
Rated voltage:
120V
Rated frequency: 60 Hz
Rated current:
2 x 6A
Power
consumption:
10W
Protection class: I
Degree of
IP 20 D to
protection:
EN 60 529, to be
guaranteed by
mounting/integration
Method of
Type 1B to
operation:
EN 60 730-1
Ambient temperature
During
operation:
0 to 40°C /
32 to 104°F
For use in boiler rooms
(normal ambient conditions)
During storage and
transport:
–20 to 65°C /
-4 to 149°F
Relay outputs at 120V for
Heating circuit
pumps or control
output
sÖ
:
2 FLA, 120 VAC
*1
Circulation
pump for heat-
ing the DHW tank
sA
:
2 FLA, 120 VAC
*1
DHW circulation
pump
sK
:
2 FLA, 120 VAC
*1
Shunt
pump
sL
:
2 FLA, 120 VAC
*1
Central fault
indicator
gÖ
:
2 FLA, 120 VAC
*1
Mixing valve
motor return
temperature
raising
or
3-way valve
DHW tank heating system
or
mixing valve
motor
gS
:
0.1 FLA,
120 VAC
*1
Burner
plug
fA
:
4 FLA, 120 VAC
plug
lÖ
:
– 2-stage
0.5 FLA 120 V~
– modulating
0.1 FLA 120 V~
*
1
Total max. 6 A 120V
5285
941
-
0
1