Installation
24
Adjustment of the adjustable high limit
(if required)
The adjustable high limit is supplied with a factory setting of 95°C.
Adjustment to 100°C / 212°F
1.
Using a suitable screwdriver,
lever out and remove the
selector knob ”
R
” behind the
hinged cover.
2.
Using a pair of pointed pliers,
break off the cams identified by
the shaded areas in the Fig.
from the stop dial.
A
75 to 100°C
167 to 212
°
F
3.
Fit the selector knob ”
R
” so
that the marking is in the centre
of the selected range.
Please note:
Note the setting of coding address
”06”!
5285
941
-
0
1
1.
2.
A
3.
If the system is operated in
conjunction with a domestic hot
water tank, ensure that the
maximum permissible domestic
hot water temperature is not
exceeded. If necessary, install a
suitable safety device for this
purpose.
WARNING