Start-up
70
Steps
(continued)
9. Match the coding addresses
(continued)
10.
Set the established values in coding
Level 1.
See page 114 for coding 1.
Address Setting of
05
the partial output (see point 8) as a percentage proportion of the
max. output; e.g.
partial output: 170 kW
max. output: 210 kW
170 kW
210 kW x100 %
=
81 %
08
units and tens digits of the maximum output established in point
4: e.g. max. output: 210 kW – here set: 10
09
hundreds digit of the maximum output established in point 4: e.g.
max. output: 210 kW – here set: 2
0A
the basic output (see point 6) as a percentage proportion of the
max. output; e.g.
basic output: 70 kW
max. output: 210 kW
70 kW
210 kW x100 %
=
33 %
15
the operating time in seconds established in point 5
Please note:
You will find details of other possible settings in the sections entitled
”Coding 1” and ”Coding 2” (see page 114 and 116).