Additional information
118
Coding 2
(continued)
Overview of all codings
(continued)
Coding as per
factory setting
Address:
Value
Function
New coding
Address:
Value
Possible change
04:
*1
Boiler/
burner
Switching differential
04: 0
04: 1
04: 2
Switching differential 4°C / 7°F
Switching differential heat demand-
controlled
ERB50 function
Values from 6 to 12°C / 11 to 22°F are
set, depending on the heat demand.
ERB80 function
Values from 6 to 20°C / 11 to 36°F are
set, depending on the heat demand.
The heat demand-controlled switching
differential takes into account the boiler
load. The switching differential, i.e. the
burner operating time, is varied in relation
to the actual heat demand.
Burner
Burner
Burner
Set-
point
Set-
point
Set-
point
Low
heat demand
Medium
heat demand
High
heat demand
Time
Time
Time
Low
heat demand
Medium
heat demand
High
heat demand
Low
heat demand
Medium
heat demand
High
heat demand
ON
OFF
ON
OFF
ON
OFF
05: 70
Boiler/
burner
(mod.)
Burner curve
05: 1
to
05: 99
Burner curve not linear:
Partial output in kW (at
g
of the
Operating time of the
actuating drive)
Max. output in kW
= Partial output in %
·x 100 %
06: 87
Boiler/
burner
Max. limit of boiler water
temperature set to 95°C /
203°F
06: 20
to
06: 127
Maximum boiler water temperature limit
variable between 20 and 127°C / 68 and
261°F
*1
The factory setting is determined by the boiler coding card.
5285
941
-