Additional information
113
System components
(continued
)
Input Module 0 to 10 V, Part No. 7134 561
From software version 7, the Input Module can be connected (software version via scan 2: 1st digit, display
7).
For external control of the boiler/supply temperature via a 0 to 10VDC signal
10 to 100°C or 30 to 120°C
(50 to 212°F or 86 to 248°F)
or
to signal reduced mode and regulate a heating circuit pump to a lower speed.
fÖ
Power connection
aVF
0 to 10VDC input
aVG
KM BUS to control unit
aBJ
Potential free output contact
A
Power supply
(provide disconnect if required by
code)
B
DIP switch (see table)
DIP switch
Function
1 to 3:
1:
2:
3:
4:
4:
OFF
ON
ON
ON
ON
OFF
Switch for pre-set value
Reduced mode – system circuit A1
Reduced mode – mixing valve circuit M2
Reduced mode – mixing valve circuit M3
Pre-set value default 10 to 100°C / 50 to 212°F
Pre-set value default 30 to 120°C / 86 to 248°F
Please note:
Amongst switches 1 to 3, only
one
switch may be set to ON.
5285
941
-
0
1
OFF
A
Electronics
24V 5V
L1
40
120 VAC
157
144
145
N
S Ö P
1 2 3
1 2 3
1 2 3 4
ON
F1
50mA
B
_ +
(slow)