Additional information
133
Coding 2
(continued)
Overview of all codings
(continued)
Coding as per
factory setting
Address: Value
Function
New coding
Adress:
Value
Possible change
F9:-14
Boiler
circuit
Temperature limit for raising
reduced room temperature
set-point -14°C.
Note coding address “A3”
F9: +10
to
F9: -60
Temperature limit adjustable from
+10 to -60°C
FA: 20
Boiler
circuit/
mixing
valve
circuit
Raising of the supply
temperature when switching
reduced to normal room
temperature by 20%
FA: 0
to
FA: 50
Temperature adjustable from 0 to 50%
Fb: 30
Boiler
circuit/
mixing
valve
circuit
Time required for raising the
supply temperature (see
coding address “FA”) 60
minutes
Fb: 0
to
Fb: 150
Time adjustable from 0 to 300 minutes;
1 increment = 2 minutes