Additional information
132
Coding 2
(continued)
Overview of all codings
(continued)
Coding as per
factory setting
Address: Value
Function
New coding
Adress:
Value
Possible change
E2: 50
Boiler
circuit/
mixing
In conjunction with remote
control:
No room correction value
E2: 0
to
E2: 49
Room correction value negative
g
valve
circuit
E2: 51
to
E2: 99
Room correction value positive
F1: 0
Mixing
valve
circuit
Slab curing function not
active
F1: 1
to
F1: 4
See DIN 4725-2.
The commissioning/service report to
be completed by the heating
contractor must contain the
following data regarding heating up:
Heat-up data for the
corresponding supply temperatures
Max. supply temperature reached
Operating status and outdoor
temperature on handing-over the
installation
Slab curing function selectable on
basis of four temperature/time
curves (see page 134).
Please note:
Refer to the data and instructions
provided by the floor slab
manufacturer.
The function is resumed after a
power failure or after the control
unit is switched off.
When the slab curing function has
terminated or the address is reset
manually to 0, the ”
rw
” heating
program is switched on.
F2: 8
Boiler
circuit
Time limit for party mode
8 hours
F2: 0
No time limit for party mode
F2: 1
to
F2: 12
Time limit for party mode variable
between 1 and 12 hours
F8:-5
Boiler
circuit
Temperature limit for
cancelling reduced mode
-5°C.
F8: +10
to
F8: -60
Temperature limit adjustable from
+10 to -60°C
Note coding address “A3”
F8: -61
Function inactive
5285
941
-
0
1