Additional information
130
Coding 2
(continued)
Overview of all codings
(continued)
Coding as per
factory setting
Address: Value
Function
New coding
Address:
Value
Possible change
b6: 0
*1
Boiler
circuit/
mixing
valve
circuit
In conjunction with remote
control in RS mode:
Without rapid heat-up/fast
setback
b6: 1
With rapid heat-up/fast setback
Fast setback:
Only possible with weather-compensated
operation with the room temperature sensor
switched on or with pure room temperature
dependent control.
The desired room temperature
value must be reduced by at least 2 K by
Pressing the energy saving button ”S”
Switching over from normal
heating to reduced operation
Optimized switch-off.
Fast setback is ended when the desired room
temperature is reached.
Rapid heat-up:
Only possible with weather-compensated
operation with the room temperature sensor
switched on or with pure room temperature
dependent control.
The desired room temperature value must be
increased by at least 2 K by
Pressing the party button
Switching over from reduced operation to
normal heating
Optimized switch-on.
Rapid heat-up is ended when the desired
room temperature is reached.
b7: 0
Boiler
circuit/
mixing
In conjunction with remote
control in RS mode:
Without learning optimized
b7: 1
With optimized switch-on time
(max. time shift 2 hours 30 min.)
mixing
valve
circuit
Without learning optimized
switch-on time
b7: 2
With optimized switch-on time
(max. time shift 15 hours 50 min.)
b8: 10
Boiler
circuit/
mixing
valve
circuit
In conjunction with remote
control in RS mode:
Heat-up gradient: 10
minutes/Kelvin
b8: 11
to
b8: 255
Heat-up gradient for optimized switch-on time
variable between 11 and 255 minutes/Kelvin
b9: 0
*1
Boiler
circuit/
mixing
valve
circuit
Without learning optimized
switch-on time
b9: 1
With learning optimized switch-on time
5285
941
-
0
1