Installation
When extending wire, there is the
possibility of exposure to
electromagnetic interference. Avoid
running wires beside or near high
voltage 120/240 VAC conductors.
If proximity to high voltage
conductors cannot be avoided, use
stranded, twisted pair or shield design
wire. Ensure that only one end of the
shielding is grounded.
WARNING
25
Connection of the outdoor temperature sensor
The outdoor temperature sensor should be mounted 2 to 2.5 metres / 6.5 to
8 ft above ground level on the north or north-west facing wall of the building.
In the case of multi-storey buildings, it should be mounted in the upper half of
the second storey.
Make sure that the sensor is not located over windows, doors and air vents,
nor immediately beneath a balcony or guttering.
Do not paint over the outdoor temperature sensor housing.
1.
Remove the cap.
2.
Mount the bottom part of the
sensor housing.
3.
Pull the sensor wire through the
opening in the terminal
compartment and through the
strain relief provided.
4.
Connect the wires to the
terminals.
5.
Place the cap over the outdoor
temperature sensor.
5285
941
-
0
1
2.
5.
1.
4.
3.
Resistance
in
400
420
440
460
480
500
520
540
560
580
600
-40
-30
-20
-10
0
10
20
30
-40
-22
-4
14
32
50
68
86
Outdoor temperature sensor °C / °F