Additional information
119
Coding 2
(continued)
Overview of all codings
(continued)
Coding as per
factory setting
Address:
Value
Function
New coding
Address:
Value
Possible change
08:
*1
Boiler/
burner
Max. output of burner in kW 08: 1
to
08: 99
Maximum output variable
from 1 to 99 kW;
1 increment = 1 kW
09:
*1
Boiler/
burner
Max. output of burner in kW 09: 1
to
09: 199
Maximum output variable
from 1 to 19900 kW;
1 increment = 100 kW
0A:
*1
Boiler/
burner
Basic output of burner in %
0A: 0
to
0A: 100
Basic output in %
Basic output in kW
Max. output in kW x100%
=
0b: 0
Boiler
Boiler protection when boiler
released
0b: 1
to
0b: 98
Boiler protection is switched off after
1 to 98 hours without request
0b: 99
Boiler protection at all times
0C: 0
Boiler
Without function
0C: 1
Continuous return temperature control
0d: 1
Boiler
With Therm-Control,
effective for mixing valve of
0d: 0
Without Therm-Control
effective for mixing valve of
heating circuits
0d: 2
Without function
13:
*1
Boiler/
burner
Switch-off differential
The burner is switched off
13: 0
Without switch-off differential
burner
The burner is switched off
when the boiler water
temperature rises above the
desired value
13: 1
to
13: 20
Switch-off differential variable from
1 to 20°C/ 2 to 36°F
14:
*1
Burner
Minimum operating time
14: 1
to
14: 15
Minimum operating time variable from 1 to 15
minutes
15: 10
*2
Boiler/
burner
(mod.)
Operating time of actuating
drive 10 seconds
15: 5
to
15: 199
Operating time variable
from 5 to 199 seconds
16:
*1
(Mod.)
burner
Mod. burner offset in K
Temporary reduction of the
boiler set-point value after
burner start
16: 0
to
16: 15
Offset during optimized start-up
adjustable from 0 to 15°C / 0 to 27°F
1A:
*1
(Mod.)
burner
Optimized start-up in
minutes
1A: 0
to
1A: 60
Duration of optimized start-up
adjustable from 0 to 60 minutes
1b: 60
Burner
Time from ignition of burner
to start of control 60
seconds
1b: 0
to
1b: 199
Control delay adjustable
from 0 to 199 seconds