125
Coding 2
(continued)
Overview of all codings
(continued)
Coding as per
factory setting
Address: Value
Function
New coding
Address:
Value
Possible change
88: 0
General
Temperatures displayed in
Celsius
88: 1
Temperatures displayed in Fahrenheit
89: 1
General
Automatic participant
recognition on KM-BUS
89: 0
No participant reognition
8A: 175
General
Display of codings which
can be set for the system
type concerned
8A: 176
All codings displayed regardless of system type
and equipment installed
8E: 4
General
Display and
acknowledgment of faults:
8E: 0
Only on the programming unit of the control
unit
g
on the programming unit and
all Vitotrol remote controls
installed
8E: 1
On the programming unit of the control unit
and on the remote control for system circuit
A1
8E: 2
On the programming unit of the control unit
and on the remote control for mixing valve
circuit M2
8E: 3
On the programming unit of the control unit
and on the remote control for mixing valve
circuit M3
90: 128
General
Time constant for
calculating the outdoor
temperature change
21.3 hours
90: 0
to
90: 199
Fast matching (lower values) or slow matching
(higher values) of the supply temperature to
the change in the outdoor temperature
according to the selected value;
1 increment = 10 minutes
91: 0
General
Without changeover of the
heating program
91: 1
With changeover of the heating program
(connection via plug
aVD
):
Changeover effective for: System circuit A1
91: 2
Mixing valve circuit M2
91: 3
System circuit A1 and mixing valve circuit M2
91: 4
Mixing valve circuit M3
91: 5
System circuit A1 and mixing valve circuit M3
91: 6
Mixing valve circuits M2 and M3
91: 7
All heating circuits (A1, M2, M3)
92: 165
General
Do not adjust!
Will only display if coding
address “8A: 176” is set
93: 0
General
Central fault indication in
emissions test mode/service
display not effective for
central fault
93: 1
Central fault indication in emissions test
mode/service display effective for central fault
94: 0
General
Without plug-in adaptor for
external safety equipment
94: 1
With plug-in adaptor for external safety
equipment; recognized automatically
96: 1
General
With mixing valve extension
circuit board
96: 0
Without mixing valve extension circuit board
5285
941
-
0
1