Coding
Code 2
(cont.)
Coding in the delivered condition
Possible change
Boiler circuit/mixer circuit
C8
:
31
*1
With remote control unit
and for the heating circuit,
operation with room
temperature hook−up must
be encoded:
Without limiting room
influence
C8
:
1
to
C8
:
30
Room influence limit
adjustable from 1 to 30 K
Mixer circuit
C9
:
0
Control of an underfloor
heating system by flow and
return temperature sensor:
Without heat−up phase
C9
:
1
With optimisation during
the heat−up phase
(operated with coding
address C7)
Boiler circuit/mixer circuit
d3
:
14
Do not adjust
d4
:
0
j
d5
:
0
The heating program
changes to
Constant
operation with reduced
room temperature
d5
:
1
The heating program
changes to
Constant
central heating with
standard room
temperature
E1
:
1
With remote control:
Set day value is adjustable
at the remote control unit
E1
:
0
Set day value adjustable
from 3 to 23
º
C
from 10 to 30
º
C
E1
:
2
Set day value adjustable
from 17 to 37
º
C
*1
Change the code for the heating circuit without mixer A1 for boilers without lower
temperature limit or for mixer circuit M2, if the remote control unit affects that
heating circuit.