28
Commissioning
Adjusting heating curves
(cont.)
Adjust the set room temperature
(for each heating circuit separately)
Standard room temperature:
Select the set day temperature with
the set value adjuster.
The value will be automatically
adopted after approx. 2s.
Reduced room temperature:
1.
Call up the set night temperature
with
E
.
2.
Change the value with
a
or
b
.
3.
Confirm the set value with
d
.
Examples
Adjustment of the standard room
temperature from 20
º
C to 26
º
C
Adjustment of the reduced room
temperature from 5
º
C to 14
º
C
A
Boiler water temperature or flow
temperature in
º
C
B
Outside temperature in
º
C
C
Set room temperature in
º
C
D
Heating circuit pump OFF
E
Heating circuit pump ON
Accordingly, the heating curve is
adjusted along the set room
temperature axis, which results in
modified start/shutdown
characteristics of the heating circuit
pumps, if the heating circuit pump
logic is activated.
5862700GB