Coding
Code 2
(cont.)
Coding in the delivered condition
Possible change
Boiler circuit/mixer circuit
F2
:
0
No time limit for party
mode
*1
F2
:
1
to
F2
:
12
Time limit for party mode
adjustable from 1 to 12h
*1
F8
:
5
For operation in reduced
room temperature mode,
the set room temperature
will be raised (up to the
temperature limit set by
coding address F9) to a
value subject to the outside
temperature if the outside
F8
:
+10
to
F8
:
60
Temperature limit for
cancelling reduced mode,
adjustable from
+10 to 60
º
C
temperature, if the outside
temperature falls below
5
º
C.
Observe the setting of
coding address A3.
F8
:
61
Function disabled
F9
:
14
Below an outside
temperature of 14
º
C, the
set room temperature will
be raised to the value
selected as set room
temperature, if the system
is in standard room
temperature mode
F9
:
+10
to
F9
:
60
Limit for raising the set
room temperature to the
value selected for standard
mode, adjustable from
+10 to 60
º
C
FA
:
20
Raising the set flow
temperature for the
transition from reduced
temperature mode to
standard room
temperature mode by
about 20%
FA
:
0
to
F9
:
50
Raising the set flow
temperature for the
transition from reduced
temperature mode to
standard room
temperature mode
adjustable from 0 to 50%
Fb
:
30
Duration for raising the set
flow temperature (see
coding address FA): 60min
Fb
:
0
to
Fb
:
150
Duration for raising the set
flow temperature
adjustable from 0 to
300min;
1 setting step
¢
2min
*1
Party mode ends
automatically
in the
Heating and DHW
program, when the system
changes over to operation with standard room temperature.