Components
Components from the parts list
(cont.)
Outside temperature sensor
Connection
See page 16.
Checking the outside temperature
sensor
1.
Pull plug
!
.
2.
Check the sensor resistance at
terminals 1 and 2 of the plug.
3.
Disconnect cores from the sensor,
if actual values deviate severely
from the curve, repeat the sensor
test and compare the results with
the actual temperature (for
scanning, see page 31).
4.
Subject to result, replace the lead
or outside temperature sensor.
5.
Scan actual temperature
(see page 31).
Specification
Protection level:
IP 43
Permiss. ambient
temperature during
operation, storage
and transport:
40 to + 70
º
C
5862700GB
R
esistance in
400
420
440
460
480
500
520
540
560
580
600
−40 −30 −20 −10
0
10
20
30
Outside temperature in
º