81
Coding
Code 1
(cont.)
Coding in the delivered condition
Possible change
Summer funct. A1
A5 : 5
With heating circuit pump
logic function
A5 : 0
Without heating circuit
pump logic function
Slope A1
d3 : 14
Do not adjust
Level A1
d4 : 0
Do not adjust
DHW priority M2
A2 : 2
Cylinder priority
A2 : 0
Without cylinder priority
y
p
y
applicable to heating
circuit pump and mixer
A2 : 1
Cylinder priority only
applicable to mixer
A2 : 3
to
A2 : 15
Modulating cylinder
priority
Summer funct. M2
A5 : 5
With heating circuit pump
logic function
A5 : 0
Without heating circuit
pump logic function
Min. supply temp. M2
C5: 20
Electronic minimum flow
temperature limit 20
º
C
C5: 1
to
C5 : 127
Minimum limit adjustable
from 1 to 127
º
C (only for
operation with standard
room temperature)
Max. supply. temp. M2
C6: 75
Electronic maximum limit
of the flow temperature
set to 75
º
C
C6: 1
to
C6 : 127
Maximum limit adjustable
from 1 to 127
º
C
Slope M2
d3 : 14
Do not adjust
Level M2
d4 : 0
Do not adjust
5862700GB