88
Coding
Code 2
(cont.)
Coding in the delivered condition
Possible change
DHW
(cont.)
70
:
0
DHW circulation pump ON
according to time program
when DHW heating is
enabled
70
:
1
DHW circulation pump
output only subject to time
program
71
:
0
DHW circulation pump:
ON according to time
program
71
:
1
OFF during DHW heating to
first set value
p
g
71
:
2
ON during DHW heating to
set value 1
72
:
0
72
:
1
OFF during DHW heating to
set value 2
72
:
2
ON during DHW heating to
set value 2
73
:
0
73
:
1
to
73
:6
During time program
1 x/h for 5min ON
to
6 x/h for 5min ON
73
:
7
Constantly ON
74
:
5
With control module V:
DHW circulation pump ON
for 5min via zero volt
contact
74
:
0
to
74
:15
Start−up time adjustable
from 0 to 15min
75
:
0
DHW circulation pump:
ON during economy and
standby mode and
according to time program
75
:
1
OFF during economy mode
5862700GB