110
Specification
Specification
Rated voltage:
230 V~
Rated
frequency:
50 Hz
Rated current:
6 A ~
Power
consumption:
5 W
Safety class:
I
Protection level: IP 20 D to EN60529;
safeguard through
appropriate design
and installation
Function:
Type 1 B to
EN607301
Permissible
ambient
temperature
H
in operation: 0 to 40
º
C
Use in living space
and boiler rooms
(standard ambient
conditions)
H
during storage
and transport: 20 to 65
º
C
Rated capacity of relay outputs at
230 V~ for
H
Heating circuit
pumps
sÖ
:
4 (2) A~
*1
H
Cylinder storage
system
sA
:
4 (2) A~
*1
H
DHW circulation
pump
sK
:
4 (2) A~
*1
H
Mixer motor
gS
:
0.2 (0.1) A~
*1
H
Burner
plug
fA
:
4 (2) A~
Plug
lÖ
:
two−stage:
1 (0.5) A~
modulating:
0.1 (0.05) A~
H
Total:
max. 6 A~
*
1
Total max. 4 A
~
5862700GB