96
Coding
Code 2
(cont.)
Coding in the delivered condition
Possible change
Boiler circuit/mixer circuit
(cont.)
b7
:
0
*1
With remote control unit
and for the heating circuit,
operation with room
temperature hook−up must
be encoded:
Without start−up time
optimisation
b7
:
1
With start−up time optimisation
(max. offset 2h 30min)
p
b7
:
2
With start−up time optimisation
(max. offset 15h 50min)
b8
:
10
*1
With remote control unit
and for the heating circuit,
heating with room
temperature hook−up must
be encoded:
Heat−up gradient
Start−up time optimisation
10min/K
b8
:
11
to
b8
:
255
Heat−up gradient start−up
time optimisation adjustable
from 11 to 255min/K
b9
:
0
*1
With remote control unit
and for the heating circuit,
heating with room
temperature hook−up must
be encoded:
Without learning start−up
time optimisation
b9
:
1
With learning start−up time
optimisation
C0
:
0
*1
With remote control:
Without shutdown time
optimisation
C0
:
1
With shutdown time
optimisation (max. offset 1h)
p
C0
:
2
With shutdown time
optimisation (max. offset 2h)
C1
:
0
*1
With remote control:
Without shutdown time
optimisation
C1
:
1
to
C1
:
12
With shutdown time
optimisation (max. offset
10 to 120min)
1 setting step
¢
10min
*1
Change the code for the heating circuit without mixer A1 for boilers without lower
temperature limit or for mixer circuit M2, if the remote control unit affects that
heating circuit.
5862700GB