37
Troubleshooting
Faults which are displayed at the programming unit
(cont.)
Fault
code
System
characteristics
Cause
Remedy
0f
Control mode
Maintenance
0F is only displayed
in the fault history
Carry out
maintenance
Note
Set code 24:0 after
maintenance.
10
Activates after 0
º
C
outside temperature
Short circuit
Outside temperature
sensor
Check outside
temperature sensor
(see page 60)
18
Lead broken
Outside temperature
sensor
(
p g
)
20
Mixer closes
Short circuit
Flow temperature
sensor
Check flow
temperature sensor
(see page 63)
21
Control without
return temperature
influence
Short circuit
Return temperature
sensor
Check return
temperature sensor
(see page 63)
28
Mixer closes
Lead broken
Flow temperature
sensor
Check flow
temperature sensor
(see page 63)
29
Control without
return temperature
influence
Lead broken
Return temperature
sensor
Check return
temperature sensor
(see page 63)
30
H
with DHW cylinder:
Cylinder primary
pump ON; boiler
will be held at set
DHW cylinder
temperature
Short circuit
Boiler temperature
sensor
Check boiler
temperature sensor
(see page 59)
38
temperature
H
without DHW
cylinder:
Boiler is regulated
by control
thermostat
Lead broken
Boiler temperature
sensor
5862700GB