86
Coding
Code 2
(cont.)
Coding in the delivered condition
Possible change
Boiler/burner
(cont.)
33
:
0
With control module V:
During external burner
demand, pumps and mixer
remain in control mode
33
:
1
All pumps OFF,
mixer closed
General
54
:
0
Without solar control unit
54
:
1
With Vitosolic100;
will be recognised
automatically
54
:
2
With Vitosolic200;
will be recognised
automatically
DHW
55
:
0
Cylinder heating,
hysteresis
$
2.5 K
55
:
1
Adaptive cylinder heating
active
56
:
0
DHW temperature
adjustable from 10 to 60
º
C
56
:
1
DHW temperature
adjustable from 10 to 95
º
C
Notes
H
Observe the max.
permissible DHW
temperature.
H
Change thermostat
R
setting
58
:
0
Without auxiliary function
for DHW heating
58:
1
to
58
:
95
Input of a second set DHW
value; adjustable
from 1 to 95ºC (observe
coding address56 and the
Auxiliary function
section
on page53)
59
:
0
Cylinder heating:
Starting point
2.5K
Switch−off point +2.5K
59:
1
to
59
:
10
Starting point adjustable
from 1 to 10K below the
set value
60
:
20
During DHW heating, boiler
water temperature is max.
20K higher than set DHW
temperature
60
:
10
to
60
:
50
The difference between the
boiler water temperature
and the set DHW
temperature is adjustable
from 10 to 50 K
5862700GB