83
Coding
Code 2
(cont.)
Overall summary
Coding in the delivered condition
Possible change
System design
(see page80)
Boiler/burner
02
:
0
Operation with
single−stage burner
02
:
1
Operation with two−stage
burner
g
g
02
:
2
Operation with modulating
burner
03
:
0
Do not adjust
04
:
0
Switching hysteresis 4K
(see page103)
04
:
1
Heat demand−dependent
switching hysteresis (see
page103)
ERB50 function
(values from 6 to 12 K)
04
:
2
ERB80 function
(values from 6 to 20 K)
05:
8
Differential temperature 8 K 05
:
0
to
05
:
40
Differential temperature
adjustable from 0 to 40K
06
:
85
Maximum limit of the
boiler water temperature
set to 85
º
C
06
:
20
to
06
:
130
Maximum limit of the
boiler water temperature
adjustable from 20 to 130
º
C
0b:
0
Do not adjust
Boiler/burner (two−stage)
10
:
20
Hook−up delay
(integral) = 2 560 Ks
10
:
0
to
10
:
199
Hook−up delay for enabling
stage 2 (from stage 1) in
heating mode
adjustable
from 0 to 25
472Ks
1setting step
¢
128Ks
11
:
20
11
:
0
to
11
:
199
Hook−up delay for enabling
stage 2 (from stage 1)
during
cylinder heating
adjustable from 0 to
25
472Ks
1setting step
¢
128Ks