95
Coding
Code 2
(cont.)
Coding in the delivered condition
Possible change
Boiler circuit/mixer circuit
(cont.)
b1
:
0
Do not adjust
b2
:
8
*1
With remote control unit
and for the heating
circuit, operation with
room temperature
hook−up must be
encoded:
b2
:
0
Excluding room influence
Room influencing factor8 b2
:
1
to
b2
:
31
Room influencing factor
adjustable from 1 to 31
b3
:
0
Do not adjust
b5
:
0
*1
With remote control unit:
Without room
temperature− dependent
heating circuit pump logic
function
b5
:
1
Heating circuit pump
ON at RT
actual
< RT
set
+
D
T
OFF at RT
actual
> RT
set
+
D
T
D
T for ON
D
T for OFF
+4K
+5K
b5
:
2
+3K
+4K
b5
:
3
+2K
+3K
b5
:
4
+1K
+2K
b5
:
5
+0K
+1K
b5
:
6
1K
+0K
b5
:
7
2K
1K
b5
:
8
3K
2K
b6
:
0
*1
With remote control unit:
Without quick heat−up/
quick setback
b6
:
1
With quick heat−up/
quick setback
(see page49)
*1
Change the code for the heating circuit without mixer A1 for boilers without lower
temperature limit or for mixer circuit M2, if the remote control unit affects that
heating circuit.
5862700GB