Enable external heat source for DHW heating
Parameter
Setting
"External heat source"
Ó
"Enable external heat source for DHW heating 7B0D"
"1"
Parameters for immersion heater
Parameters
Setting
"DHW"
Ó
"Enable electric heaters for DHW heating 6015"
"1"
"Enable booster heaters for DHW heating 6014"
"1"
Parameters for swimming pool water heating
Parameter
Setting
"System definition"
Ó
"External extension 7010"
"1"
or
"3"
"Swimming pool 7008"
"1"
Parameters for ventilation with Vitovent 200-C
Parameter
Setting
"Ventilation"
Ó
"Vitovent enable 7D00"
"2"
Vitovent 200-C
Further enabling for Vitovent 200-C, if applicable
Parameter
Setting
"Ventilation"
Ó
"Enable preheater bank electric 7D01"
"0"
Defrosting without preheating coil
(
"Strategy, passive frost pro-
tection 7D2C"
)
"1"
Frost protection with preheating
coil; defrosting via bypass
"2"
Frost protection with preheating
coil; comfort function
"Strategy, passive frost protection 7D2C"
"0"
Fans OFF
"1"
Defrosting via bypass
"2"
Supply air fan OFF
"Type of heat exchanger 7D2E"
"0"
Countercurrent heat exchanger
"1"
Enthalpy heat exchanger
"Installation position 7D2F"
"0"
Ceiling mounting
"1"
Wall mounting
"Function, external 230 V input, ventilation 7D3A"
"1"
External switch (bathroom switch)
enabled
Commissioning, inspection, maintenance
Commissioning the system
(cont.)