Minimum clearances for heat pump cascades (max. 5 outdoor units)
Facing layout without partition wall
> 500
B
> 1500
A
B
A
> 500
> 500
> 500
A
B
A
B
> 500
> 500
Fig. 6
A
Air intake
B
Air discharge
Facing layout with partition wall
> 500
B
400
A
B
A
> 500
> 500
400
> 500
A
B
A
B
> 500
> 500
C
Fig. 7
A
Air intake
B
Air discharge
Single row layout
> 500
A
400
B
A
B
A
B
> 500
> 500
> 500
A
B
> 500
A
B
> 500
Fig. 8
A
Air intake
B
Air discharge
Transport and siting
!
Please note
Impacts, compression and tensile loads can
cause damage to the outside panels of the
appliance.
Never
apply loads/weight to the top, front or
side panels of the appliance.
!
Please note
If the compressor in the external unit is strongly
tilted, lubricant will enter the refrigerant circuit
and damage the appliance.
Max. tilting angle: 45°
Floorstanding installation
Foundations
Fit the floor supports on 2 horizontal foundation strips.
We recommend the construction of concrete founda-
tions in accordance with the following diagram. The
stated thickness of the layers represents an average
value. These values should be adjusted to suit the
local conditions. Follow the standard rules of building
engineering.
Installation sequence
Installing the outdoor unit
(cont.)
5790 931 GB
Installation