141
Type AWB-M/AWB-M-E-AC
201.D0
4
201.D0
6
201.D0
8
201.D1
0
201.D1
3
201.D1
6
Energy efficiency class
to EU Regulation no.
811/2013
Heating, average climatic conditions
■
Low temperature applications (W35)
A
++
A
++
A
++
A
++
A
++
A
++
■
Medium temperature applications (W55)
A
+
A
++
A
++
A
++
A
++
A
++
Performance data
as per EU Regulation No.
811/2013 (average climatic conditions)
Low temperature applications (W35)
■
Energy efficiency
η
S
%
169
170
175
175
175
175
■
Rated heating output P
rated
kW
5.37
5.59
6.84
9.32
9.98
10.61
Medium temperature applications (W55)
■
Energy efficiency
η
S
%
122
125
127
129
129
130
■
Rated heating output P
rated
kW
5.26
5.09
6.40
9.35
10.04
10.71
Sound power level to ErP
Sound power level, outdoor unit
dB(A)
53
54
55
56
56
56
400 V appliances
Type AWB/AWB-E-AC
201.D10
201.D13
201.D16
Heating performance data
to EN 14511
(A2/W35)
Rated heating output
kW
5.90
6.31
7.02
Fan speed
rpm
600
600
600
Power consumption
kW
1.44
1.59
1.78
Coefficient of performance
ε
(COP) in heating
mode
4.10
3.98
3.94
Output control
kW
3.50 to 10.50
4.00 to 11.40
4.50 to 12.00
Heating performance data
to EN 14511
(A7/W35, 5 K spread)
Rated heating output
kW
7.58
8.61
10.11
Fan speed
rpm
600
600
600
Air flow rate
m
3
/h
4500
4500
4500
Power consumption
kW
1.51
1.77
2.04
Coefficient of performance
ε
(COP) in heating
mode
5.01
4.87
4.95
Output control
kW
4.70 to 13.60
5.20 to 14.20
5.70 to 14.70
Heating performance data
to EN 14511
(A
–
7/W35)
Rated heating output
kW
10.09
10.74
11.60
Power consumption
kW
3.17
3.58
3.87
Coefficient of performance
ε
(COP) in heating
mode
3.18
3.00
3.00
Cooling performance data
to EN 14511
(A35/W7)
Rated cooling capacity
kW
4.92
6.11
7.02
Fan speed
rpm
600
600
600
Power consumption
kW
1.82
2.20
2.53
Energy efficiency ratio EER in cooling mode
2.70
2.78
2.77
Output control
kW
Up to 6.0
Up to 6.5
Up to 7.1
Specification
Specification
(cont.)
5790 931 GB
Appendix