135
Parameter
Code
Delivered condition Commission-
ing
Maintenance/
service
"Standard ventilation"
C10B
■
Vitovent 200-W:
50 %
■
Vitovent 300-C:
100 m
3
/h
■
Vitovent 300-W:
150 m
3
/h
"Intensive ventilation"
C10C
■
Vitovent 200-W:
75 %
■
Vitovent 300-C:
125 m
3
/h
■
Vitovent 300-W:
225 m
3
/h
"Background ventilation, second fan
duct"
C189
15 %
"Reduced ventilation, second fan duct"
C18A
25 %
"Standard ventilation, second fan duct"
C18B
50 %
"Intensive ventilation, second fan duct"
C18C
75 %
"Bypass mode"
C1A0
0
"Central heating and heat recovery"
C1A1
0
"Imbalance permitted"
C1A2
1
"Specified imbalance"
C1A3
0
"Set reheater coil temperature"
C1A4
210 (
≙
21 °C)
"Humidity sensor sensitivity"
C1A6
0
"Min. temperature, geothermal heat ex-
changer"
C1AA
50 (
≙
5 °C)
"Max. temperature, geothermal heat ex-
changer"
C1AB
250 (
≙
25 °C)
"Function, input 1"
C1B0
0
"Min. voltage, input 1"
C1B1
0 (10
≙
1 V)
"Min. voltage, input 2"
C1C1
0 (10
≙
1 V)
"Flow rate correction"
C1C7
100
Commissioning/service reports
Control parameter report
(cont.)
5790 931 GB
Appendix