134
Parameter
Code
Delivered condition Commission-
ing
Maintenance/
service
"Heating circuit for blocking bypass
damper"
7D21
7
"Control voltage matching"
7D27
0 (
≙
0 V)
"Fan for control voltage matching"
7D28
0
"Strategy, passive frost protection"
7D2C
0
"Type of heat exchanger"
7D2E
0
"Installation position"
7D2F
0
"Function, external 230 V input, ventila-
tion"
7D3A
0
"Duration, bathroom vent."
7D3B
30 min
"Starting block, ventilation periods part
1"
7D5E
0
"Starting block, ventilation periods part
2"
7D5F
0
"Control voltage matching, supply air
fan"
7D71
0 V
"Control voltage matching, exhaust air
fan"
7D72
0 V
"Sensor matching, outdoor air temp after
preheating coil"
7D76
0 K
"Sensor matching, supply air tempera-
ture"
7D77
0 K
"Sensor matching, extract air tempera-
ture"
7D79
0 K
Ventilation: Vitovent 200-W, Vitovent 300-C and Vitovent 300-W
Parameter
Code
Delivered condition Commission-
ing
Maintenance/
service
"Vitovent enable"
7D00
0
"Heating circuit for blocking bypass
damper"
7D21
7
"Preheater coil"
C101
1
"Reheater coil"
C102
0
"Humidity sensor"
C105
0
"Set CO2 value"
C106
0
"Bypass temperature"
C108
220 (
≙
22 °C)
"Background ventilation"
C109
■
Vitovent 200-W:
15 %
■
Vitovent 300-C:
30 m
3
/h
■
Vitovent 300-W:
50 m
3
/h
"Reduced ventilation"
C10A
■
Vitovent 200-W:
25 %
■
Vitovent 300-C:
75 m
3
/h
■
Vitovent 300-W:
100 m
3
/h
Commissioning/service reports
Control parameter report
(cont.)
5790 931 GB
Appendix