background image

 

Copyright 1999 Carrier Corporation

Form 38YZA-1PD

 

Product
Data

 

38YZA (60Hz)

Deluxe 12 SEER Split-System

Heat Pump with Puron

 

®

 

Refrigerant

 

Sizes 024 thru 060

 

 

Carrier’s technological leadership 

has risen to a new level with the 
development of the 38YZA Heat 
Pump, the outdoor section of a 
superior split heat pump system. This 
leadership effort has yielded a 
product that appeals to consumers for 
all of its unique benefits. 

 

Puron®, the environmentally sound 
refrigerant 

 

— The first unique feature 

of the 38YZA is the environmentally 
sound nature of Puron, which provides 
the homeowner with additional peace 
of mind because their heating and 
cooling system’s refrigerant has zero 
ozone-depletion potential.

Second, thanks to the performance 
advantage of Puron, the 38YZA is 
extremely efficient. In fact, the 
38YZA features some of the lowest 
energy usages of single speed heat 
pumps available from Carrier. 
Maximum performance and 
efficiency are made possible through 
the use of the FX4A and FV4A fan 
coils, Custom Made for Puron 
applications. 

Third, the cost of service will 
potentially be reduced in the future as 
the industry’s older refrigerant, R-22 
is gradually phased out through 
Federally legislated production 
limitations. 

 

FEATURES/BENEFITS

 

PressureGuard™/Ease of 
Installation 

 

— Another unique feature 

of the WeatherMaker 38YZA is the 
patent-pending PressureGuard™, 
which enables the use of line sets 
currently employed across the 
industry. For retrofit applications, 
PressureGuard prevents mandatory 
replacement of line sets. For new 

 

INTRODUCING THE WEATHERMAKER 38YZA HEAT PUMP

FEATURING PURON

 

®

 

THE ENVIRONMENTALLY SOUND REFRIGERANT

Summary of Contents for 38YZA024-30

Page 1: ...ks to the performance advantage of Puron the 38YZA is extremely efficient In fact the 38YZA features some of the lowest energy usages of single speed heat pumps available from Carrier Maximum performance and efficiency are made possible through the use of the FX4A and FV4A fan coils Custom Made for Puron applications Third the cost of service will potentially be reduced in the future as the indust...

Page 2: ...t timer and low voltage terminal board The defrost control is a time temperature initiation termination control which includes 3 field selectable time periods of 30 50 and 90 minutes Thermostatic Expansion Valve TXV This unit must be installed with a Puron TXV on the indoor coil The FX4 and FV4 indoor fan coils come factory equipped with a bi flow Puron TXV When installed in this application no fu...

Page 3: ... 8 1 1 8 7 8 3 4 RST Refrigeration Service Tubing standard refrigerant grade tubing NOTES 1 Tube diameters are for lengths up to 50 ft For tubing lengths greater than 50 ft consult the Application Guideline and Service Manual for Residential Split System Air Conditioners and Heat Pumps using Puron Refrigerant 2 Refrigerant tubes and indoor coils must be evacuated to 500 microns to minimize contami...

Page 4: ... Standard Crankcase Heater Sizes 048 060 KHAOT0301FST Outdoor Thermostat All Sizes KHAOT0201SEC Secondary Outdoor Thermostat All Sizes KHASA0101AAA Service Alarm All Sizes KHAIC0101AAA Interface Control Optimizer II All Sizes KSATX0201HSZ Bi Flow TXV Hard Shutoff Size 024 030 KSATX0301HSZ Bi Flow TXV Hard Shutoff Sizes 036 042 KSATX0401HSZ Bi Flow TXV Hard Shutoff Size 048 KSATX0501HSZ Bi Flow TXV...

Page 5: ...talled at the outdoor unit and which stops and starts refrigerant liquid flow in response to compressor operation Maintains a column of refrigerant liquid ready for action at next compressor operation cycle SUGGESTED USE In long line applications Refer to the Residential Split System Long Line Application Guideline and Service Manual 10 Low Ambient Pressure Switch A long life pressure switch which...

Page 6: ... ROMEX shall be that of 60 C 140 F conductors per the NEC ANSI NFPA 70 Article 336 26 If other than uncoated non plated 60 or 75 C 140 or 167 F insulation copper wire solid wire for 10 AWG and smaller stranded wire for larger than 10 AWG is used consult applicable tables of the NEC ANSI NFPA 70 NOTE Control circuit is 24v on all units and requires external power source Copper wire must be used fro...

Page 7: ...F 2 Maximum outdoor operating ambient in heating mode is 66 F 3 Series designation is the 13th position of the unit model number 4 Center of gravity 5 NOTES DIMENSIONS IN UNIT SIZE SERIES UNIT DIMENSIONS MINIMUM MOUNTING PAD DIMENSIONS A B C D E F G H J K L M Support Feet Snow Stand 024 0 33 13 16 22 1 2 27 1 2 2 13 16 6 15 16 21 1 2 27 7 8 5 8 8 3 16 12 13 3 4 12 20 x 27 24 x 28 030 0 27 13 16 30...

Page 8: ... 70 F AND AT RATED CFM 80 38YZA030 FX4A030 38YZA036 FX4A036 38YZA048 FX4A048 38YZA024 FX4A030 38YZA060 FX4A060 38YZA042 FX4A042 23 4 20 5 17 6 14 7 11 7 8 8 5 9 2 9 NOTE The performance shown includes the PressureGuard cycling the outdoor fan The ambient temperature that the outdoor fan cycles depends on the outdoor indoor combination indoor airflow installation practices and system maintenance al...

Page 9: ...0 20 VARIABLE SPEED FURNACE CD5AW036 937 25 000 TDR 13 00 11 20 24 600 3 52 15 200 2 38 7 70 CJ5A CK5A CK5BW036 937 25 000 TDR 13 00 11 20 24 600 3 52 15 200 2 38 7 60 COILS 58U H X V060 12 VARIABLE SPEED FURNACE CC5A CD5AA036 700 24 400 TDR 13 00 11 15 23 200 3 32 14 800 2 30 7 50 CD5AW036 700 24 400 TDR 13 00 11 15 23 200 3 32 14 800 2 30 7 50 CJ5A CK5A CK5BA036 700 24 400 TDR 13 00 11 15 23 200...

Page 10: ... 10 65 36 600 3 50 23 400 2 54 8 00 CJ5A CK5A CK5BA048 1275 34 000 NONE 12 50 10 70 36 800 3 56 23 400 2 56 8 10 CJ5A CK5A CK5BT042 1275 34 000 NONE 12 00 10 65 36 600 3 50 23 400 2 54 8 00 CJ5A CK5A CK5BT048 1275 34 000 NONE 12 50 10 70 36 800 3 56 23 400 2 56 8 10 CJ5A CK5A CK5BW048 1275 34 000 NONE 12 50 10 70 36 800 3 56 23 400 2 56 8 10 CK3BA048 1275 34 000 NONE 12 50 10 70 36 800 3 56 23 400...

Page 11: ...8 1400 39 600 NONE 12 00 10 10 39 500 3 04 26 200 2 32 7 00 CC5A CD5AW048 1500 40 000 NONE 12 00 10 25 40 500 3 28 26 400 2 38 7 60 CD3 A B A048 1500 40 000 NONE 12 00 10 25 40 500 3 28 26 400 2 38 7 60 CD5A CD5BA048 1500 40 000 NONE 12 00 10 25 40 500 3 28 26 400 2 38 7 60 CE3AA048 1400 40 500 NONE 12 00 10 35 41 500 3 32 26 400 2 40 7 60 CJ5A CK5A CK5BA048 1400 40 000 NONE 12 00 10 30 41 500 3 3...

Page 12: ...VP100 20 VARIABLE SPEED FURNACE CC5A CD5AA060 1400 44 500 TDR 13 00 11 25 47 500 3 50 27 800 2 40 8 00 CC5A CD5AW060 1400 45 000 TDR 13 00 11 45 48 000 3 54 27 800 2 44 8 20 CJ5A CK5A CK5BA060 1400 44 500 TDR 13 00 11 25 47 500 3 50 27 800 2 40 8 00 CJ5A CK5A CK5BX060 1400 45 000 TDR 13 00 11 45 48 000 3 54 27 800 2 44 8 20 CK3BA060 1400 44 500 TDR 13 00 11 25 47 500 3 50 27 800 2 40 8 00 COILS 58...

Page 13: ...for heat pumps Ratings for other combinations are determined under DOE computer simulation procedures Based on computer simulation TXV must be Puron compatible and hard shutoff type In most cases only 1 method should be used to achieve TDR function Using more than 1 method in a system may cause degradation in performance Use either the accessory Time Delay Relay KAATD0101TDR or a furnace equipped ...

Page 14: ...7 15 6 1 89 28 2 15 1 2 10 26 5 14 5 2 34 24 8 14 0 2 59 22 9 13 4 2 86 20 9 12 7 3 14 67 27 2 20 4 1 88 25 8 19 8 2 09 24 3 19 3 2 32 22 8 18 7 2 57 21 1 18 0 2 84 19 2 17 3 3 11 63 25 4 19 8 1 87 24 1 19 2 2 08 22 7 18 6 2 31 21 2 18 0 2 55 19 7 17 3 2 82 18 0 16 6 3 09 62 25 2 24 8 1 87 24 0 24 0 2 08 22 8 22 8 2 31 21 6 21 6 2 56 20 2 20 2 2 83 18 8 18 8 3 11 57 25 1 25 1 1 87 24 0 24 0 2 08 2...

Page 15: ...13 32 0 18 1 2 35 30 1 17 5 2 60 28 1 16 8 2 86 25 8 16 0 3 16 23 3 15 2 3 47 67 31 8 25 5 2 13 30 1 24 9 2 34 28 4 24 2 2 59 26 3 23 4 2 85 24 3 22 5 3 15 22 0 21 4 3 46 63 29 9 24 8 2 12 28 1 24 0 2 33 26 5 23 3 2 58 24 9 22 6 2 85 23 0 21 7 3 15 21 0 20 7 3 48 62 30 3 30 3 2 12 28 8 28 8 2 34 27 4 27 4 2 59 25 7 25 7 2 85 23 9 23 9 3 15 22 0 22 0 3 47 57 30 3 30 3 2 12 28 7 28 7 2 34 27 2 27 2 ...

Page 16: ...26 7 4 42 57 36 0 36 0 2 72 34 4 34 4 3 01 32 7 32 7 3 33 30 9 30 9 3 67 28 9 28 9 4 03 26 7 26 7 4 42 Indoor Section Size Cooling Indoor Section Size Cooling Capacity Power Capacity Power 40FKA FK4CNF 003 1 00 0 89 CJ5A CK5A CK5BA 042 1 01 0 92 005 1 03 0 89 048 1 00 0 89 CC5A CD5AA 042 1 00 1 00 COILS 58MVP080 20 VARIABLE SPEED FURNACE CC5A CD5AC 048 1 00 0 98 CC5A CD5AA 042 1 01 0 93 CC5A CD5AW...

Page 17: ... 8 3 24 43 7 33 8 3 60 40 9 32 7 3 98 38 3 31 7 4 42 35 6 30 6 4 88 33 0 29 5 5 41 63 43 2 33 8 3 22 40 8 32 7 3 57 38 6 31 8 3 97 36 2 30 7 4 40 33 7 29 6 4 88 30 9 28 3 5 38 62 43 1 42 6 3 22 40 9 40 9 3 57 39 1 39 1 3 98 37 1 37 1 4 41 34 8 34 8 4 89 32 3 32 3 5 40 57 43 0 43 0 3 22 41 0 41 0 3 58 39 2 39 2 3 98 37 1 37 1 4 42 34 9 34 9 4 90 32 4 32 4 5 41 Indoor Section Size Cooling Indoor Sec...

Page 18: ...5 86 67 53 4 40 4 3 54 51 0 39 4 3 91 48 1 38 3 4 31 45 5 37 3 4 77 42 7 36 1 5 27 39 7 35 0 5 83 63 49 9 39 1 3 51 47 7 38 2 3 88 45 0 37 0 4 28 42 5 35 9 4 73 39 9 34 9 5 24 37 0 33 6 5 81 62 49 8 49 4 3 51 47 6 47 6 3 87 45 5 45 5 4 28 43 3 43 3 4 74 41 2 41 2 5 26 38 5 38 5 5 81 57 49 8 49 8 3 51 47 7 47 7 3 88 45 6 45 6 4 29 43 5 43 5 4 75 40 9 40 9 5 24 38 4 38 4 5 79 Indoor Section Size Coo...

Page 19: ... 95 48 4 38 5 7 68 63 61 1 44 2 4 60 58 0 42 8 5 08 55 5 41 7 5 65 52 5 40 4 6 26 49 3 39 0 6 93 45 6 37 4 7 66 62 60 3 55 1 4 59 57 3 53 6 5 07 54 6 52 3 5 62 51 7 50 8 6 23 48 8 48 8 6 90 45 8 45 8 7 64 57 58 7 58 7 4 57 56 2 56 2 5 06 54 0 54 0 5 61 51 5 51 5 6 23 48 9 48 9 6 91 45 9 45 9 7 65 2000 72 69 9 36 1 4 79 66 5 34 9 5 29 63 6 33 9 5 85 60 5 32 8 6 48 56 6 31 4 7 14 52 3 29 9 7 87 67 6...

Page 20: ... 07 15 0 13 7 2 11 17 4 15 5 2 15 20 2 18 4 2 21 23 2 23 2 2 28 26 3 26 3 2 53 27 8 27 8 2 62 825 11 0 10 1 2 10 13 0 11 9 2 09 15 3 13 9 2 11 17 7 15 7 2 14 20 6 18 7 2 18 23 7 23 7 2 24 26 8 26 8 2 47 28 5 28 5 2 54 950 11 1 10 3 2 15 13 2 12 1 2 13 15 5 14 1 2 12 18 0 16 0 2 14 20 8 19 0 2 17 24 1 24 1 2 22 27 7 27 3 2 44 28 5 28 5 2 46 Indoor Section Size Heating Indoor Section Size Heating Ca...

Page 21: ...38 24 8 22 6 2 46 29 1 29 1 2 55 29 4 29 4 2 72 30 8 30 8 2 78 1050 12 1 11 2 2 28 14 8 13 6 2 30 17 8 16 3 2 34 21 3 18 9 2 39 25 2 23 0 2 46 29 6 29 6 2 53 30 0 30 0 2 68 31 5 31 5 2 73 1200 12 3 11 3 2 35 15 0 13 8 2 35 18 1 16 5 2 38 21 6 19 2 2 41 25 6 23 3 2 47 30 1 30 1 2 53 30 5 30 5 2 67 32 1 32 1 2 70 Indoor Section Size Heating Indoor Section Size Heating Capacity Power Capacity Power F...

Page 22: ... Section Size Heating Indoor Section Size Heating Capacity Power Capacity Power FX4ANF 036 1 00 1 00 CJ5A CK5A CK5BA 042 0 99 0 97 40FKA FK4CNF 003 0 95 0 94 048 0 97 0 96 005 0 95 0 86 COILS 58MVP080 20 VARIABLE SPEED FURNACE CC5A CD5AA 042 0 99 1 01 CC5A CD5AA 042 0 99 0 98 CC5A CD5AC 048 0 98 1 02 CD5AA 048 1 00 0 97 CC5A CD5AW 042 0 98 1 01 CJ5A CK5A CK5BA 042 0 99 0 98 048 0 98 0 98 048 0 97 ...

Page 23: ... 39 5 4 03 38 5 38 5 3 94 1400 18 9 17 4 3 20 22 3 20 5 3 28 26 3 24 0 3 38 30 7 27 2 3 49 35 5 32 3 3 62 40 9 40 9 3 76 40 2 40 2 3 98 39 3 39 3 3 87 1575 18 9 17 4 3 27 22 6 20 8 3 34 26 7 24 3 3 42 31 1 27 6 3 52 36 0 32 8 3 63 41 5 41 5 3 75 40 8 40 8 3 95 40 0 40 0 3 83 Indoor Section Size Heating Indoor Section Size Heating Capacity Power Capacity Power FX4ANF 042 1 02 1 01 COILS 58MVP080 20...

Page 24: ...52 5 52 5 4 70 1600 19 5 17 9 3 61 23 6 21 7 3 67 28 6 26 0 3 78 34 1 30 3 3 93 40 6 37 0 4 10 48 1 48 1 4 30 55 8 55 8 4 67 54 6 54 6 4 64 1800 19 7 18 1 3 71 24 0 22 0 3 76 28 9 26 4 3 84 34 6 30 7 3 97 41 2 37 5 4 13 48 8 48 8 4 31 55 8 55 8 4 67 54 6 54 6 4 61 Indoor Section Size Heating Indoor Section Size Heating Capacity Power Capacity Power FX4ANF 048 1 01 1 06 COILS 58MVP100 20 VARIABLE S...

Page 25: ...6 59 0 59 0 4 74 57 0 57 0 4 75 2000 26 6 24 5 4 07 32 5 29 9 4 22 38 7 35 2 4 34 45 3 40 3 4 47 53 1 48 3 4 64 61 7 61 7 4 84 59 9 59 9 4 69 58 1 58 1 4 68 2250 26 9 24 7 4 19 32 9 30 3 4 33 39 1 35 7 4 41 45 9 40 8 4 52 53 8 48 9 4 67 62 6 62 6 4 85 60 8 60 8 4 68 59 1 59 1 4 65 70 1750 25 7 23 6 4 07 31 7 29 2 4 32 37 8 34 5 4 50 44 3 39 3 4 68 51 7 47 1 4 88 60 0 60 0 5 11 58 1 58 1 4 98 56 1 ...

Page 26: ...or coil below 150 ft see items 8 and 9 following 8 For interconnecting refrigerant tube lengths greater than 50 ft and or elevation differences between indoor and outdoor units greater than 20 ft consult Residential Split System Application Guideline and Service Manual for Air Conditioners and Heat Pumps using Puron refrigerant 9 If ANY refrigerant tubing is buried provide a minimum 6 in vertical ...

Page 27: ...27 ...

Page 28: ... 99 Manufacturer reserves the right to discontinue or change at any time specifications or designs without notice and without incurring obligations Book 1 4 Page 28 Catalog No 523 760 Printed in U S A PC 101 Form 38YZA 1PD Tab 5a 5a Replaces NEW ...

Reviews: