13
Weight of outdoor units
Vitocal 200-S
Type
Weight in kg
230 V appliances
■
AWB-M
■
AWB-M-E-AC
201.D04
94
201.D06
94
201.D08
99
201.D10
136.5
201.D13
136.5
201.D16
136.5
400 V appliances
■
AWB
■
AWB-E-AC
201.D10
148
201.D13
148
201.D16
148
Installation location
■
Select a site with good air circulation, so that the
cooled air can dissipate and be replaced by warm
air.
■
Never install in the corners of rooms, in recesses or
between walls. This could result in an "air short cir-
cuit" between the air being discharged and the air
being drawn in.
!
Please note
An "air short circuit" during
heating mode
will
result in the cooled discharged air re-entering
the unit. This can result in reduced heat pump
efficiency and defrosting problems.
Avoid "air short circuits".
!
Please note
An "air short circuit" during
cooling mode
will
result in the heated discharged air re-entering
the unit. This can lead to high pressure faults.
Avoid "air short circuits".
■
If siting the appliance in a location that is exposed to
wind, ensure that the wind cannot influence the fan
area. Strong wind can have a negative influence on
the air flow through the evaporator.
■
Take the lengths of the refrigerant lines into account:
see "Connecting the refrigerant lines".
■
Select an installation location where the evaporator
cannot be blocked by leaves, snow, etc.
■
Select the installation location giving due considera-
tion to the physical laws concerning the propagation
and reflection of sound.
Technical guide
■
Never install next to or below bedroom windows.
■
Maintain a clearance of at least 3 m to pathways,
downpipes or sealed surfaces. The cooled air in the
discharge area creates a risk of ice forming when
outside temperatures are below 10 °C.
■
The installation location must be easily accessible,
for example for maintenance work: see "minimum
clearances".
Installation sequence
Installing the outdoor unit
(cont.)
5790 931 GB
Installation