49
Outdoor unit power supply 230 V~
Type AWB-M/AWB-M-E-AC 201.D04 to D16
GND Rx/Tx-Rx/Tx+
Modbus
L
N
A
B
L3 N
?
?
Fig. 48
A
Outdoor unit wiring chamber: See page 20.
B
Power supply 230 V/50 Hz
Max. cable length
Vitocal 200-S
Type
Cable
Max. cable length
230 V appliances
■
AWB-M
■
AWB-M-E-AC
201.D04
3 x 2.5 mm
2
29 m
201.D06
3 x 2.5 mm
2
25 m
201.D08
3 x 2.5 mm
2
25 m
201.D10
3 x 2.5 mm
2
20 m
or
3 x 4.0 mm
2
32 m
201.D13
3 x 4.0 mm
2
20 m
or
3 x 6.0 mm
2
30 m
201.D16
3 x 4.0 mm
2
20 m
or
3 x 6.0 mm
2
30 m
Max. fuse rating
Type AWB-M/AWB-M-E-AC
201.D04
201.D06
201.D08
201.D10
201.D13
201.D16
20 A
20 A
25 A
25 A
32 A
32 A
Outdoor unit power supply 400 V~
!
Please note
Incorrect phase sequence can cause damage to
the appliance.
Make the compressor power supply
only
in the
phase sequence specified (see terminals) with a
clockwise
rotating field.
Installation sequence
Power supply
(cont.)
5790 931 GB
Installation