129
DHW
Parameter
Code
Delivered condition Commission-
ing
Maintenance/
service
"Set DHW temperature"
6000
500 (
≙
50 °C)
"Min. DHW temperature"
6005
100 (
≙
10 °C)
"Max. DHW temperature"
6006
600 (
≙
60 °C)
"Hysteresis DHW temperature heat
pump"
6007
50 (
≙
5 K)
"Hysteresis DHW temperature booster
heater"
6008
100 (
≙
10 K)
"Start optimisation for DHW heating"
6009
0
"Stop optimisation for DHW heating"
600A
0
"Set DHW temperature 2"
600C
600 (
≙
60 °C)
"Temperature rise per hour for DHW
heating"
600D
30 K/h
"Temperature sensor at bottom of DHW
cylinder"
600E
0
"Max. runtime DHW heating in heating
mode"
6011
240 (
≙
24 min)
"Max. interruption of DHW heating for
central heating"
6012
90 (
≙
9 min)
"Enable booster heaters for DHW heat-
ing"
6014
0
"Enable electric heaters for DHW heat-
ing"
6015
0
"Priority DHW heating with combi cylin-
der"
6016
0
"Start attempts for DHW after high pres-
sure shutdown"
6017
0
"Shutdown hysteresis inst. heating water
heater"
601E
10 (
≙
1 K)
"Enable elec. heating/ext. HS for reheat-
ing only"
6040
0
Solar
Parameter
Code
Delivered condition Commission-
ing
Maintenance/
Service
"Type solar control unit"
7A00
0
Parameters for solar control module, type
SM1
C0xx
These parameters will only be displayed if the solar
control module, type SM1, is connected to the heat
pump and
"Type solar control unit"
is set to
"3"
.
For a description of the parameters, see installation
and service instructions for "solar control module, type
SM1".
Commissioning/service reports
Control parameter report
(cont.)
5790 931 GB
Appendix