35
F
Controller and sensor PCB: See page 41.
G
Connection for bus cable to outdoor unit (Modbus)
Indoor unit: main PCB (230 V~ components)
Information regarding the connection values
■
The specified output is the recommended connected
load.
■
Total output of all components connected directly to
the heat pump control unit (e.g. pumps, valves, mes-
sage facilities, contactors):
Max.
1000 W
If the total output is < 1000 W, the individual rating of
a component (e.g. pump, valve, message facility,
contactor) can be greater than specified. However,
the breaking capacity of the relevant relay must not
be exceeded.
■
The specified current indicates the max. switching
current of the switching contact. Observe total cur-
rent of 5 A.
Set the required parameters during commissioning:
See page 66 onwards.
Plug
sYA
Terminals
Function
Explanation
211.2
1.
Secondary pump
■
In systems without a heating water buffer cylinder, no
other heating circuit pump is required: See terminal
212.2.
■
Connect a temperature limiter to restrict the maximum
temperature for underfloor heating circuits (if instal-
led) in series.
Connection values
■
Output: 140 W
■
Voltage: 230 V~
■
Max. control current: 4(2) A
211.3
r
1.
Instantaneous heating water heater
switching, stage 1
Connection values
■
Output: 10 W
■
Voltage: 230 V~
■
Max. control current: 4(2) A
211.4
M
r
■
3-way diverter valve "Central heat-
ing/DHW heating"
Connection values
■
Output: 130 W
■
Voltage: 230 V~
■
Max. control current: 4(2) A
Note
Depending on the heat pump and system version, not
all components may be installed: See "DHW heating
connections".
■
Cylinder loading pump
M
■
2-way shut-off valve
211.5
AC
Type AWB(-M)-E-AC:
3-way diverter valves for heating wa-
ter buffer cylinder bypass in cooling
mode
Connect the 3-way diverter valves for the heating water
buffer cylinder bypass in parallel.
Connection values
■
Output: 10 W
■
Voltage: 230 V~
■
Max. control current: 4(2) A
Installation sequence
Electrical connection
(cont.)
5790 931 GB
Installation