74
Further enabling for Vitovent 300-F, if applicable
Parameter
Setting
"Ventilation"
Ó
"Enable preheater bank electric 7D01"
"1"
"Enable reheater bank hydraulic 7D02"
"1"
"Enable humidity sensor 7D05"
"1"
"Enable CO2 sensor 7D06"
"1"
"Type of heat exchanger 7D2E"
"0"
Countercurrent heat exchanger
"1"
Enthalpy heat exchanger
Adjust values for Vitovent 300-F, if necessary
Parameter
Setting
"Ventilation"
Ó
"Set extract air temperature 7D08"
"100"
to
"300"
(
≙
10 to 30 °C)
"Flow rate reduced ventilation 7D0A"
Subject to sizing
Ventilation unit service instruc-
tions
"Flow rate nominal ventilation 7D0B"
"Flow rate intensive ventilation 7D0C"
Parameters for utilisation of power generated on site
Parameter
Setting
"Photovoltaics"
Ó
"Enable own energy consumption PV 7E00"
"1"
"Threshold for electrical power 7E04"
"0"
to
"300"
(
≙
0 to 30 kW)
Enable required functions for utilisation of power generated on site
Parameter
Setting
"Photovoltaics"
Ó
"Enable own energy consumptn for set DHW temperature 2
7E10"
"1"
"Enable own energy consumption for DHW heating 7E11"
"1"
"Enable own energy consumptn for heating water buffer cyl.
7E12"
"1"
"Enable own energy consumption for heating 7E13"
"1"
"Enable own energy consumption for cooling 7E15"
"1"
Specify the temperature differential to the selected set value for the chosen function
Parameter
Setting
"Photovoltaics"
Ó
"Raise set DHW cylinder temperature PV 7E21"
"0"
to
"500"
(
≙
0 to 50 K)
"Raise set heating water buffer cylinder temp PV 7E22"
"0"
to
"400"
(
≙
0 to 40 K)
"Raise set room temperature PV 7E23"
"0"
to
"100"
(
≙
0 to 10 K)
"Reduce set room temperature PV 7E25"
"0"
to
"100"
(
≙
0 to 10 K)
Commissioning, inspection, maintenance
Commissioning the system
(cont.)