142
Type AWB/AWB-E-AC
201.D10
201.D13
201.D16
Cooling performance data
to EN 14511
(A35/W18)
Rated cooling capacity
kW
6.20
7.55
10.00
Fan speed
rpm
600
600
600
Power consumption
kW
1.77
2.29
3.57
Energy efficiency ratio EER in cooling mode
3.50
3.30
2.80
Output control
kW
Up to 8.0
Up to 9.5
Up to 10.5
Air intake temperature
Cooling mode (type AWB-E-AC only)
■
Min.
°C
15
15
15
■
Max.
°C
35
35
35
Heating mode
■
Min.
°C
–
20
–
20
–
20
■
Max.
°C
35
35
35
Heating water
(secondary circuit)
Minimum flow rate
l/h
1400
1400
1400
Minimum volume in the heating system, can-
not be fitted with shut-off devices
l
50
50
50
Max. external pressure drop (RFH) at mini-
mum flow rate
mbar
500
500
500
kPa
50
50
50
Max. flow temperature
°C
60
60
60
Outdoor unit electrical values
Rated voltage, compressor
3/N/PE 400 V/50 Hz
Max. operating current, compressor
A
8.7
8.7
8.7
Starting current, compressor
A
15
15
15
Fuse rating
A
16
16
16
IP rating
IPX4
IPX4
IPX4
Indoor unit electrical values
Heat pump control unit/PCB
■
Rated voltage, control unit/PCB
1/N/PE 230 V/50 Hz
■
Power supply fuse rating
1 x B16A
■
Internal fuse
6.3 A (slow)/250 V
Instantaneous heating water heater
■
Type AWB-E-AC:
Factory-fitted
■
Type AWB:
Accessories
■
Rated voltage
1/N/PE 230 V/50 Hz
or
3/N/PE 400 V/50 Hz
■
Heating output
kW
9
■
Power supply fuse rating
3 x B16 A
Specification
Specification
(cont.)
5790 931 GB