Connecting the temperature limiter, part no. 7151 728,
7151 729
B
to the mixer extension kit
M
1~
C
B
A
sÖ
sÖ
N
?
Fig. 36
A
Connect plug
sÖ
to the extension kit.
B
Temperature limiter
C
Heating circuit pump M3/HC3
Indoor unit: expansion PCB on main PCB (230 V~ components)
Information regarding the connection values
■
The specified output is the recommended connected
load.
■
The total output of all components connected directly
to the heat pump control unit (e.g. pumps, valves,
message facilities, contactors):
max.
1000 W
If the total output is < 1000 W, the individual rating of
a component (e.g. pump, valve, message facility,
contactor) can be greater than specified. However,
the breaking capacity of the corresponding relay
must not be exceeded.
■
The specified current indicates the max. switching
current of the switching contact. Observe total cur-
rent of 5 A.
■
Safety LV is unsuitable for controlling external heat
generators.
Set the required parameters during commissioning:
See page 66 onwards.
Plug
sXS
Terminals
Function
Explanation
222.1
Switching mixer motor for external
heat generator
Signal mixer CLOSE
Connection values:
■
Output: 10 W
■
Voltage: 230 V~
■
Max. switching current: 0.2(0.1) A
222.2
Switching mixer motor for external
heat generator
Signal mixer OPEN
Connection values:
■
Output: 10 W
■
Voltage: 230 V~
■
Max. switching current: 0.2(0.1) A
Installation sequence
Electrical connection
(cont.)