Figure 37:
Typical Master Ground Bar Terminations (cont’d on next page)
Master Ground
Bar Location
Master Ground Bar Layout and Designation Plan
2 AWG
PTS
GND
6 AWG
Enclo-
sure /
Equip-
ment
GND
6 AWG
Enclo-
sure /
Equip-
ment
GND
4/0 AWG
Plant RTN
2 AWG
Ext
GND
Bar
2 AWG
Ext
GND
Bar
2 AWG
FIF Rack
GND
2 AWG
Power
Rack
GND
2 AWG
FIF Rack
GND
Cables may be dressed from top or
bottom if required by physical cable layout.
Termination locations space horizontally for 4/0 cable lugs of 1.200” maximum
width allow for 0.125” minimum space between adjacent lugs. Busbar
mounting detail omitted for clarity.
Keep cables in same section
of busbar as shown above.