INITIAL POWER UP
Important Safety Instructions
DANGER!
Adhere to the “Important Safety Instructions” presented at the front of this document.
Safety Precautions
DANGER!
RISK OF ELECTRICAL SHOCK, GENERAL
All ground connections must be installed and verified prior to turning-up of the WIC.
DANGER!
RISK OF ELECTRICAL SHOCK, AC
Proper actions, include, but not limited to:
a)
Verify before contacting the WIC that no current leakage or ground fault condition is present.
b)
Verify a proper ground is in place.
CAUTION!
PREVENT EQUIPMENT DAMAGE, FROM CONDENSATION
Until the WIC is turned up for service, maintain WIC sealing to prevent weather and moisture entry.
Provide humidity control (i.e.: two 150 W incandescent bulbs) as required.
Once the WIC is operational, the WIC system will maintain interior conditions.
Prerequisite
Verify that all procedures and safety notices previous to this section have been applied regarding the WIC,
system grounding, AC power, DC power, and battery installation.
Verify that all procedures and safety notices accompanying customer-installed equipment have been applied.
Verify that the WIC has an approved connection to the local utility power supply.
CAUTION!
Prevent Equipment Damage: connect only 200 A, 240 VAC, 1-PH, 3 wire supply.