Application
The XTE 802 Series Walk-In-Cabinet (WIC) is designed to house and protect environmentally sensitive
electronics at telecommunications sites including cellular, microwave radio, BBU pools for CRAN, and edge
applications with virtualized networks.
•
The XTE 802 Series Walk-In-Cabinet (WIC) is designed to provide secure and water-tight housing for
equipment, power and batteries supporting wireless and wireline telecommunications applications.
•
The XTE 802 Series Walk-In-Cabinet (WIC) depends upon a proven structural system and integrated
mechanical components.
•
The XTE 802 Series Walk-In-Cabinet (WIC) has several mounting options, primarily helical and concrete
pier.
Standards Compliance
The XTE 802 Series Walk-In-Cabinet (WIC) is designed to meet the following standards where applicable:
•
CSA Certificate of Compliance #70096774.
-
CLASS - C321111 - INDUSTRIAL CONTROL EQUIPMENT - Enclosures for Electrical Equipment
-
CLASS - C321191 - INDUSTRIAL CONTROL EQUIPMENT - Enclosures for Electrical Equipment – US
-
Enclosure Type 3R
NOTE!
The WIC is intended for industrial and/or power distribution equipment applications. These
components are intended for the installation of industrial electrical equipment and/or power distribution
equipment where the complete assembly is approved for installation in non-hazardous locations in
accordance with the National Electric Code (NEC) and Canadian Electric Code (CEC).
APPLICABLE REQUIREMENTS
a)
CSA C22.2 No, 94.1-07 / UL 50 12th Ed (Harmonized) Enclosures for Electrical Equipment, Non-
Environmental Considerations.
b)
CSA C22.2 No. 94.2-07 / UL 50E 1st Ed (Harmonized) Enclosures for Electrical Equipment,
Environmental Considerations.
•
National Building Code - Canada, 2005.
•
National Building Code - USA, 2012.
•
ASTM A653 - Galvanized Steel.
•
Welding Conformance to CWB - CSA Standard W47.1 and AWS – D1.2, D1.3 and D1.6.
•
Designed to Meet Seismic Zone 4.
•
Telcordia GR487 compliant for corrosion, water intrusion, ultraviolet radiation, and impact resistance.
•
DC Power System - UL Listed 1801, cUL, NEBS Level 3.
•
Power Transfer Load Center (PTLC) – constructed in accordance with UL 67 Standard for Panelboards.
Suitable for use as Service Entrance.
•
Automatic Power Transfer Switch: UL Listed to UL 1008, Standard for Transfer Switching Equipment.