B-2
ValcoMelton
Appendix B - Power Requirements
MM125 - D-90 Hot Melt Unit
System Power Requirement
Calculation - D-90 Units -
Continued
6.
Add the power requirements of hose #6 and gun #6. Compare
this value to the maximum wattage given in Line 6 of Table 1.
7.
Add the power requirements of all hoses and all guns. Compare
this value to the maximum wattage for all hoses and guns given
in Line 7 of Table 1.
8.
If any of the power requirements calculated in steps 1-7 exceed
any of the maximum allowable wattages given in Table 1, the
hose length or gun configuration must be changed, to reduce all
power requirements to below maximum-allowable wattages.
If each of the power requirements calculated in steps 1-7 is
below the maximum allowable wattages given in Table 1, the
system power requirement is within allowable limits.
Summary of Contents for D-90
Page 29: ...4 5 ValcoMelton Section 4 Installation MM125 D 90 Hot Melt Unit Electrical Panel ...
Page 49: ...5 10 Valco Cincinnati Inc Section 5 Setup MM125 D 90 Hot Melt Unit Set Language Continued ...
Page 50: ...5 11 Valco Cincinnati Inc Section 5 Setup MM125 D 90 Hot Melt Unit Set Temperature Units ...
Page 56: ...5 17 Valco Cincinnati Inc Section 5 Setup MM125 D 90 Hot Melt Unit Ready Delay Time Continued ...
Page 73: ...5 34 Valco Cincinnati Inc Section 5 Setup MM125 D 90 Hot Melt Unit Sequential Start Valve ...
Page 146: ...C 2 ValcoMelton Appendix C Schematics MM125 D 90 Hot Melt Unit 240V 3Ø 029XX435 ...
Page 147: ...C 3 ValcoMelton Appendix C Schematics MM125 D 90 Hot Melt Unit 240V 3Ø 029XX435 ...
Page 148: ...C 4 ValcoMelton Appendix C Schematics MM125 D 90 Hot Melt Unit ...
Page 149: ...C 5 ValcoMelton Appendix C Schematics MM125 D 90 Hot Melt Unit ...
Page 150: ...C 6 ValcoMelton Appendix C Schematics MM125 D 90 Hot Melt Unit ...