Set a value for parameter P3.17.3 Fire Mode Fre-
quency
8.00 Hz...P3.3.1.2 (MaxFreqRef)
3
Activate the signal when the contact opens or when
it closes
0 = Open contact
1 = Closed contact
4
Set a value for parameters P3.17.4 Fire Mode Acti-
vation on OPEN / P3.17.5 Fire Mode Activation on
CLOSE
Make a selection of a digital input to activate
Fire mode. See also Chapter 10.15 Fire mode.
5
Set a value for parameter P3.17.6 Fire Mode
Reverse
Make a selection of a digital input to activate
the reverse direction in Fire mode.
DigIn Slot0.1 = FORWARD
DigIn Slot0.2 = REVERSE
6
Set a value for P3.17.1 Fire Mode Password
Set a password to enable the Fire mode func-
tion.
1234 = Enable test mode
1001 = Enable Fire mode