P3.9.29 RESPONSE TO SAFE TORQUE OFF (STO) FAULT (ID 775)
Use this parameter to select the response of the drive to a 'STO Fault'.
This parameter defines the response for F30 – Safe Torque Off (Fault ID: 530).
This parameter defines drive operation when Safe Torque Off (STO) function is activated (e.g.
emergency stop button has been pressed or some other STO operation has been activated).
0 = No action
1 = Alarm
2 = Fault, stop by coasting
NOTE!
This parameter is not visible if the drive does not have support for safety torque off
functionality.
10.10
AUTOMATIC RESET
P3.10.1 AUTOMATIC RESET (ID 731)
Use this parameter to enable the Automatic reset function.
To select faults that are reset automatically, give the value 0 or 1 to parameters from P3.10.6
to P3.10.14.
NOTE!
The automatic reset function is available only for some fault types.
P3.10.2 RESTART FUNCTION (ID 719)
Use this parameter to select the start mode for the Automatic reset function.
P3.10.3 WAIT TIME (ID 717)
Use this parameter to set the wait time before the first reset is done.
P3.10.4 AUTOMATIC RESET: TRIAL TIME (ID 718)
Use this parameter to set the trial time for the automatic reset function.
During the trial time, the automatic reset function tries to reset the faults that occur. The
time count starts from the first automatic reset. The next fault starts the trial time count
again.
P3.10.5 NUMBER OF TRIALS (ID 759)
Use this parameter to set the total number of autoreset trials.
If the number of trials during the trial time is more than the value of this parameter, a
permanent fault shows. If not, the fault goes out of view after the trial time is completed.
VACON · 160
PARAMETER DESCRIPTIONS
10
TEL. +358 (0)201 2121 · FAX +358 (0)201 212 205