Table 2: Quick Setup parameter group
Index
Parameter
Min
Max
Unit
Default
ID
Description
P1.1
Motor Nominal Volt-
age
Varies
Varies
V
Varies
110
Find this value U
n
on
the nameplate of the
motor.
See P3.1.1.1.
P1.2
Motor Nominal Fre-
quency
8.0
320.0
Hz
50
111
Find this value f
n
on
the nameplate of the
motor.
See P3.1.1.2.
P1.3
Motor Nominal
Speed
24
19200
rpm
Varies
112
Find this value n
n
on
the nameplate of the
motor.
P1.4
Motor Nominal Cur-
rent
Varies
Varies
A
Varies
113
Find this value I
n
on
the nameplate of the
motor.
P1.5
Motor Cos Phi
0.30
1.00
Varies
120
Find this value on the
nameplate of the
motor.
P1.6
Motor nominal power
Varies
Varies
kW
Varies
116
Find this value n
n
on
the nameplate of the
motor.
P1.7
Motor Current Limit
Varies
Varies
A
Varies
107
The maximum motor
current from the AC
drive.
P1.8
Minimum Frequency
0.00
P1.9
Hz
Varies
101
The minimum fre-
quency reference that
is acceptable.
P1.9
Maximum Frequency
P1.8
320.00
Hz
50.00
102
The maximum fre-
quency reference that
is acceptable.
P1.10
I/O Control Refer-
ence A Selection
1
8
6
117
The selection of the
frequency reference
source when the con-
trol place is I/O A.
See P3.3.3 for selec-
tions.
P1.11
Preset frequency 1
P3.3.1
300.00
Hz
10.00
105
Select with the digital
input: Preset frequency
selection 0 (P3.5.1.15)
(Default = Digital Input
4)
QUICK STARTUP GUIDE
VACON · 17