P3.5.1.29 MOTOR 4 INTERLOCK (ID 429)
Use this parameter to select the digital input signal that is used as interlock signal for the
Multi-pump system.
P3.5.1.30 MOTOR 5 INTERLOCK (ID 430)
Use this parameter to select the digital input signal that is used as interlock signal for the
Multi-pump system.
P3.5.1.31 MOTOR POTENTIOMETER UP (ID 418)
Use this parameter to increase the output frequency with a digital input signal.
The motor potentiometer reference INCREASES until the contact is open.
P3.5.1.32 MOTOR POTENTIOMETER DOWN (ID 417)
Use this parameter to decrease the output frequency with a digital input signal.
The motor potentiometer reference DECREASES until the contact is open.
P3.5.1.33 ACC/DEC TIME SELECTION (ID 408)
Use this parameter to select the digital input signal that selects the ramp time to be used.
P3.5.1.34 FIELDBUS CONTROL (ID 411)
Use this parameter to select the digital input signal that switches the control place and the
frequency reference source to Fieldbus (from I/O A, I/O B or Local control).
P3.5.1.39 FIRE MODE ACTIVATION OPEN (ID 1596)
Use this parameter to select the digital input signal that activates the Fire Mode function.
P3.5.1.42 KEYPAD CONTROL (ID 410)
Use this parameter to select the digital input signal that switches the control place and the
frequency reference source to Keypad (from any control place).
P3.5.1.43 RESET KWH TRIP COUNTER (ID 1053)
Use this parameter to select the digital input signal that resets the kWh Trip Counter.
P3.5.1.44 FIRE MODE PRESET FREQUENCY SELECTION 0 (ID 15531)
Use this parameter to select the digital input signal that is used as a selector for fire mode
preset frequencies.
P3.5.1.45 FIRE MODE PRESET FREQUENCY SELECTION 1 (ID 15532)
Use this parameter to select the digital input signal that is used as a selector for fire mode
preset frequencies.
PARAMETER DESCRIPTIONS
VACON · 141
24-HOUR S358 (0)201 212 575 · EMAIL: [email protected]